The RCH01 is a wireless controller for underfloor heating circuit manifolds.

The controller has five electronic outputs for regulating the temperature of five control zones. A maximum of 18 thermo-electrical actuators and one circulation pump can be connected.

A wireless temperature sensor ST01 can be paired with each output. If the temperature sensor detects deviations from a set temperature, a sensor telegram is transmitted and the relevant RCH01 output is activated.

RCH01E5005-01-29K
Technical specifications
Coding Easywave
1 ST01 in I/O mode can be programmed per output.
Frequency 868,30 MHz
Channels 5
Power supply 230 V AC, 50 Hz
Power consumption max 0.5 W
Operating modes Heating circuit control
Outputs 5 electronic switching outputs
1 relay contacts (pump)
Total load max. 20W per output
Maximum contact load Valve actuators:
transistor control (Only resistive load permitted!)
Outputs 1 - 4: max. 4 valve actuators
Output 5: max. 2 valve actuators
max. 20 W total load per output

Pump:
resistive load (cosφ = 1.0): 5.0 A / 1,150 VA
inductive load (cosφ = 0.8): 4.0 A / 920 VA
Degree of protection IP55 (in delivery condition)
Operating temperature 0 °C to +60 °C
Dimensions (W/L/H) 180/94/57 mm
Scope of delivery
  • Radio control
  • Mounting material
  • Operating manual
Accessories (optional)
ACC-ANT50-03-21P External antenna, 868 Mhz, 5m coaxial cable, clamp connection, magnetic base

ACC-ANT50-03-21P
Models
Product number Description
RCH01E5005-01-29K Radio control for heating circuits, Easywave, 230V, 5x thermostats + circulation pump, potential loaded