RCH01 Radio control for heating circuits 230V
The RCH01 is a wireless controller for underfloor heating circuit manifolds.
The controller has five electronic outputs for regulating the temperature of five control zones. A maximum of 18 thermo-electrical actuators and one circulation pump can be connected.
A wireless temperature sensor ST01 can be paired with each output. If the temperature sensor detects deviations from a set temperature, a sensor telegram is transmitted and the relevant RCH01 output is activated.
The controller has five electronic outputs for regulating the temperature of five control zones. A maximum of 18 thermo-electrical actuators and one circulation pump can be connected.
A wireless temperature sensor ST01 can be paired with each output. If the temperature sensor detects deviations from a set temperature, a sensor telegram is transmitted and the relevant RCH01 output is activated.
Technical specifications
Coding | Easywave 1 ST01 in I/O mode can be programmed per output. |
Frequency | 868,30 MHz |
Channels | 5 |
Power supply | 230 V AC, 50 Hz |
Power consumption | max 0.5 W |
Operating modes | Heating circuit control |
Outputs | 5 electronic switching outputs 1 relay contacts (pump) |
Total load | max. 20W per output |
Maximum contact load | Valve actuators: transistor control (Only resistive load permitted!) Outputs 1 - 4: max. 4 valve actuators Output 5: max. 2 valve actuators max. 20 W total load per output Pump: resistive load (cosφ = 1.0): 5.0 A / 1,150 VA inductive load (cosφ = 0.8): 4.0 A / 920 VA |
Degree of protection | IP55 (in delivery condition) |
Operating temperature | 0 °C to +60 °C |
Dimensions (W/L/H) | 180/94/57 mm |
Scope of delivery
- Radio control
- Mounting material
- Operating manual
Accessories (optional)
ACC-ANT50-03-21P | External antenna, 868 Mhz, 5m coaxial cable, clamp connection, magnetic base |

ACC-ANT50-03-21P
Models
Product number | Description |
---|---|
RCH01E5005-01-29K | Radio control for heating circuits, Easywave, 230V, 5x thermostats + circulation pump, potential loaded |
Wiring diagram